 | PD-12 Detector type gas detector 
 A suction type ATEX detector with a very strong design. Suitable to detect a wide range of flammable and toxic gases in industrial applications and locations with limited access. A unique detector in an ATEX enclosure with built in pump. There are 3 models available: 
 PD-12A for measurement of combustible gases in ppm range PD-12B for measurement of combustible gases in %LEL range PD-12C for measurement of combustible gases in %vol. range 
 Also available as SIL 1 version. | 
- Small and lightweight with concentration and alarm display
- Extractive type with hydrogen explosion proof (Ex d IIB + H2 T4X)
- Detecting decreased flow rate function except PD-12C (option)
- Environmental friendly product
- Water and dust-proof construction (Degree of protection: IP65)
| Detectable gases | |
|---|---|
| 1,1,1,3,3-Pentafluorobutane | C4H5F5 | 
| Acetone | C3H6O | 
| Acetylene | C2H2 | 
| Butane | C4H10 | 
| Carbon dioxide | CO2 | 
| Carbon monoxide | CO | 
| Cyclohexane | C6H12 | 
| Ethanol | CH3CH2OH | 
| Ethylene | C2H4 | 
| Gasoline | Benzin | 
| Helium | He | 
| Hydrogen | H2 | 
| Isobutane | C4H10 | 
| Isopropyl alcohol | C3H8O | 
| LPG | LPG | 
| Methane | CH4 | 
| Methane | CH4 | 
| Methanol | CH4O | 
| n-Btane | C4H8 | 
| Oxygen | O2 | 
| Propane | C3H8 | 
| Propylene | C3H6 | 
| Model | PD-12A | PD-12B | PD-12C | 
|---|---|---|---|
| Detection Principle | Hot wire semiconductor | Catalytic combustion | Thermal conductivity | 
| Measuring unit | ppm | %LEL | %vol. | 
| Gas Detected | As per specifications | ||
| Sampling Method | As per specifications | ||
| Suction Flow | Over 0.5L/min | ||
| Detection Range | As per specifications | ||
| Alarm Set Value | As per specifications | ||
| Alarm Accuracy | Combustible gas: ±25% of alarm set value under identical conditions | ||
| Toxic gas: ±30% of alarm set value under identical conditions | |||
| Alarm Delay | Combustible gas: Within 30 seconds with 1.6 times of alarm set conditions | ||
| Toxic gas: Within 60 seconds with 1.6 times of alarm set concentration | |||
| Alarms | Gas alarm: Red LED lamp flashes | ||
| Trouble alarm: Yellow LED lamp flashes (sensor disconnection, sensor zero drop,power supply voltage error, etc.) | |||
| Display | Four-digit digital LED display | ||
| Output | Gas concentration analog signal | ||
| ・4-20mADC (common to the negative side of power supply) | |||
| Gas alarm contact or failure contact*1 (one stage only) | |||
| ・1a no-voltage contact output, Non-latching | |||
| ・Rated load: 0.5A at 250VAC or 0.5A at 30VDC (resistance load) | |||
| Operation | At 4 points of magnetic switches | ||
| Explosion-proof | II 2G Ex d IIB + H2 T4 Gb (ATEX)*2 | ||
| Ex d IIB + H2 T4 X (TIIS) | |||
| Degree of Protection | IP65 | ||
| Applicable Cable | Cable outer diameter: 10.5mm to 14.5mm | ||
| 6-conductor shielded cable: CVV-S 1.25mm2 or 2.0mm2 | |||
| Operating | -10 to +50 °C | ||
| Temperature/Humidity*3 | 10 to 90 %RH (0 to 50 °C) | ||
| Power Supply | 24 VDC (±20%) | ||
| Power Consumption | 7.5W max. | ||
| Dimensions | W133 x H260 x D132 mm (excluding protrusions) | ||
| Weight | Approx. 5.2kg | ||
*1 Gas alarm contact is a standard issue. Please specify if you wish a failure contact. 
*2 Some are not ATEX approved. For further information, please ask. 
*3 No radical temperature or humidity changes and no condensing.
CE Declaration of Conformity
 
                                                         
                    
                    
                    
                                                        